A
A.1
Parameter list
A-835
Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
1500:8
No. of speed setpoint filters (ARM SRM)
No. of velocity setpoint filters (SLM)
Min
Standard
Max
Unit
Data type
Effective
0
0
2
–
Unsigned16
immed.
... specifies the number of speed setpoint filters.
The filter type (bandstop or low pass PT1/PT2) is set using P1501:8.
0
No speed setpoint filter active
1
Filter 1 active
2
Filters 1 and 2 active
Note:
If filter 1 is parameterized as low pass filter, (PT1 or PT2, P1501:8), it can be switched out/
switched in using the ”First speed setpoint filter off” input signal. When parameterized as band-
stop filter, the input signal has no effect.
The speed setpoint filters are described in:
References: /FBA/, Description of Functions, Drive Functions, Section DD2
1501:8
Type of speed setpoint filter (ARM SRM)
Type of velocity setpoint filter (SLM)
Min
Standard
Max
Unit
Data type
Effective
0
0
8303
Hex
Unsigned16
immed.
... specifies the type of the 2nd speed setpont filter
Bit 0
Filter 1: Low pass/bandstop
= 1
Bandstop (filter parameters: P1514:8, P1515:8, P1516:8)
= 0
Low pass (filter parameters: P1502:8, P1506:8, P1507:8)
Bit 1
Filter 2: Low pass/bandstop
= 1
Bandstop (filter parameters: P1517:8, P1518:8, P1519:8)
= 0
Lowpass (filter parameters: P1503:8, P1508:8, P1509:8)
Bit 8
Filter 1: Low pass PT1/PT2
= 1
PT1 low pass (filter parameter: P1502:8)
= 0
PT2 low pass (filter parameters: P1506:8, P1507:8)
Bit 9
Filter 2: Low pass PT1/PT2
= 1
PT1 low pass (filter parameter: P1503:8)
= 0
PT2 low pass (filter parameter: P1508:8, P1509:8)
Bit 15
Bandstop, transformation type (from SW 3.3)
= 1
Z transformation
= 0
Bilinear transformation (standard)
Note:
Before parameterizing the filter type, the appropriate filter parameters must be assigned.
The speed setpoint filters are described in:
References: /FBA/, Description of Functions, Drive Functions, Section DD2
1502:8
Time constant, speed setpoint filter 1 (ARM SRM)
Time constant, velocity setpoint filter 1 (SLM)
Min
Standard
Max
Unit
Data type
Effective
0.0
0.0
500.0
ms
Floating Point
immed.
Note:
The filter can be switched out/switched in via the ”First speed setpoint filter off” input signal.
The speed setpoint filters are described in:
References: /FBA/, Description of Functions, Drive Functions, Section DD2
A Lists
01.99
! 611ue diff !
04.05