5
5.8
Motion Control with PROFIBUS–DP (from SW 3.1)
5-299
Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
General prerequisites:
The interpolation clock cycle (P1010) must be parameterized the
same for all axes.
The master application clock cycle T
MAPC
must be an integer multi-
ple of the interpolation clock cycle.
T
I
and T
O
must be the same for all axes.
T
DP
must be less than or equal to 16 ms.
For masters, which cannot generate a master sign of life (e.g.
SIMATIC S7), T
MAPC
must be = to T
DP
and the sign–of–life monitor-
ing in operation must be disabled using P0879.8 = 1.
Additional prerequisites for SIMATIC S7:
Presently, there is no run level that is in synchronism with DP cycle
in S7 user programs. This means, that if axes are to be simulta-
neously started, in addition to the clock–synchronous PROFIBUS
operation, the ”classic” SYNC mechanism must be used.
SYNC mechanism
––>
refer to the documentation of the DP master SIMATIC S7
(SFC 11 ”DPSYNC_FR”)
The SYNC mechanism may only be activated after the drive has set
the status bit ZSW1.9 ”control requested”.
Requirements
5 Communications via PROFIBUS DP
08.99