List of faults and warnings
7-633
Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
030
S7 communication error. Supplementary info: \%X
Cause
A fatal communication error was identified, or the drive software is no
longer consistent. The cause is erroneous communications or a hard-
ware fault on the control module.
Supplementary information: only for siemens-internal error diagnostics
Remedy
– Implement noise suppression measures (screening, check ground
connections, ...)
– Replace control module
Acknowledgement POWER ON
Stop response
STOP II (SRM, SLM) STOP I (ARM)
031
Internal data error. Suppl. info: \%X
Cause
Error in the internal data, e.g. errors in the element/block lists (incorrect
formats, ...). The drive software is no longer consistant. The cause is
propably a hardware fault on the control module.
Supplementary information: only for siemens-internal error diagnostics
Remedy
– Re-load drive software
– Replace control module
Acknowledgement POWER ON
Stop response
STOP II (SRM, SLM) STOP I (ARM)
032
Incorrect number of current setpoint filters
Cause
An illegal number of current setpoint filters was entered (> 4) (maxi-
mum number = 4).
Remedy
Correct number of current setpoint filters (P1200).
Acknowledgement POWER ON
Stop response
STOP II (SRM, SLM) STOP I (ARM)
033
Incorrect number of speed setpoint filters
Cause
An inadmissible number of speed setpoint filters (> 2) was entered
(max. number = 2).
Remedy
Correct number of speed setpoint filters (P1500)
Acknowledgement POWER ON
Stop response
STOP II (SRM, SLM) STOP I (ARM)
034
Axis count function has failed
Cause
The function for determining the number of axes that physically exist on
the power section has calculated an illegal value.
Remedy
Check that the control module is correctly inserted in the power section
or whether the power section is defective.
Acknowledgement POWER ON
Stop response
STOP II (SRM, SLM) STOP I (ARM)