SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
1151
Reset time flux controller (ARM)
Min
Standard
Max
Unit
Data type
Effective
0.0
10.0
500.0
ms
Floating Point
immed. (ARM)
1160
Threshold speed flux sensing (ARM)
Min
Standard
Max
Unit
Data type
Effective
200.0
1500.0
100000.0
rpm
Floating Point
immed. (ARM)
1161
Fixed DC link voltage
Min
Standard
Max
Unit
Data type
Effective
0
0
700
V(pk)
Unsigned16
immed.
... a fixed DC link voltage can be entered.
> 0
Fixed DC link voltage, the measurement in P1701 (DC link voltage) is inactive
0
The measurement in P1701 is active
The fixed DC link reference is calculated in instead of the measurement:
– DC link adaption
– Flux sensing (ARM)
– Field weakening and stall torque (ARM)
Note:
The DC link is measured in the I/R module, and is transferred as analog signal to the
”SIMODRIVE 611 universal” via the unit bus for evaluation.
1162
Min. DC link voltage
Min
Standard
Max
Unit
Data type
Effective
0
0
800
V(pk)
Unsigned16
immed.
... defines the permissible DC link voltage lower limit. Fault 616 is output if this limit is fallen be-
low.
1163
Max. DC link voltage
Min
Standard
Max
Unit
Data type
Effective
0
800
800
V(pk)
Unsigned16
immed.
... defines the permissible DC link voltage upper limit. Fault 617 is output if this limit is ex-
ceeded.
1164
Hysteresis, DC link monitoring
(–> 8.1)
Min
Standard
Max
Unit
Data type
Effective
0
50
600
V(pk)
Unsigned16
immed.
... defines the hysteresis for the DC link voltage monitoring. This parameter refers to parameter
1162..
1170
Pole pair width (SLM)
Min
Standard
Max
Unit
Data type
Effective
0.0
72.0
1000.0
mm
Floating Point
PO
(SLM)
The pole pair width of a linear drive corresponds to the length from a north and south pole of
the magnet.