A.1
Parameter list
A-750
Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
0205:8
Balancing filter, speed feedforward control (deadtime)
Min
Standard
Max
Unit
Data type
Effective
0.0
0.0
10.0
ms
Floating Point
immed.
... allows the time characteristics of the closed speed control loop to be simulated using a dead-
time.
The entered value is limited to two position controller cycles (P1009).
Note: refer to the index entry ”speed feedforward control”
0206:8
Balancing filter, speed feedforward control (PT1)
Min
Standard
Max
Unit
Data type
Effective
0.0
0.0
100.0
ms
Floating Point
immed.
... permits, in addition to P0205:8, the closed speed control loop to be simulated using a PT1
filter (low pass).
Note: refer to the index entry ”speed feedforward control”
0210:8
Time constant, position setpoint filter
Min
Standard
Max
Unit
Data type
Effective
0.0
0.0
1000.0
ms
Floating Point
immed.
... is the time constant of the PT1 position setpoint filter.
The effective Kv factor (position loop gain) can be reduced using the filter.
Note: refer to the index entry ”speed feedforward control”
0231
Position actual value inversion
Min
Standard
Max
Unit
Data type
Effective
0
0
1
–
Unsigned16
PO
... the control sense of the position controller is established.
1
Position actual value inversion
0
No position actual value inversion
If the position controller control sense is not OK, then the position actual value must be in-
verted.
The direction of motion is set using P0232 (position setpoint inversion).
Note: refer to the index entry ”Direction adaptation”
0232
Position setpoint inversion
Min
Standard
Max
Unit
Data type
Effective
0
0
1
–
Unsigned16
PO
... the required motion direction is set.
1
Position setpoint inversion
0
No position setpoint inversion
Note:
The control direction of the position controller remains unaffected, i.e. it is internally taken into
account (refer to the index entry ”Direction adaptation”).
0236
Spindle pitch
Min
Standard
Max
Unit
Data type
Effective
1
10000
8388607
MSR/rev
Unsigned32
PO
Note: refer to the index entry ”Encoder adaptation”
0237:8
Encoder revolutions
Min
Standard
Max
Unit
Data type
Effective
1
1
8388607
–
Unsigned32
PO
... specifies the ratio (Ü) between the encoder and load.
Ü = P0237:8 / P0238:8
Note: refer to the index entry ”Encoder adaptation”