SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
0672
Function, input terminal I0.B
(–> 3.3)
Min
Standard
Max
Unit
Data type
Effective
0
0
86
–
Unsigned16
immed.
... defines the function of input terminal I0.B, drive B for the direct measuring system of drive A.
Note:
The function number from the ”List of input signals” is entered.
Prerequisite: P0250 = 1 (direct measuring system)
The following functions can be executed via I0.B:
– External block change (function number 67)
– Flying measurement/length measurement (function number 80)
– Equivalent zero mark (function number 79)
0676
Assignment, inputs: Optional TERMINAL module
(–> 4.1)
Min
Standard
Max
Unit
Data type
Effective
0
0
3
–
Unsigned16
immed.
... defines which input terminals on the optional TERMINAL module are assigned to this drive.
0
none
1
Input terminal I4 to I7
2
Input terminals I8 to I11
3
Input terminals I4 to I11
Note:
The terminals can only be assigned to a drive once.
Prerequisite for the assignment: P0875 = 1
Assignment, outputs: Refer to P0696
0678
Image of the input terminals
Min
Standard
Max
Unit
Data type
Effective
–
–
–
Hex
Unsigned16
RO
The signal statuses of the input terminals are displayed using these parameters.
bit 15 (t. 63/t. 48), bit 14 (t. 663), bit 13 (t. 64), bit 12 (t. 65.x),
bit 11 (t. I11), bit 10 (t. I10), bit 9 (t. I9), bit 8 (t. I8),
bit 7 (t. I7), bit 6 (t. I6), bit 5 (t. I5), bit 4 (t. I4),
bit 3 (t. I3.x), bit 2 (t. I2.x), bit 1 (t. I1.x), bit 0 (t. I0.x)
Bit x = ”1” ––> input terminal has signal status ”1”
Bit x = ”0” ––> input terminal has signal status ”0”
Example: P0678 = F004 ––> Term. 63/Term. 48, Term. 663, Term. 64, Term. 65.x and Term.
I2.x have signal status ”1”
Note:
Non-assigned bits are displayed with ”0”.
Terminal I4 to terminal I11 are on the optional TERMINAL module.
0680
Signaling function of output terminal O0.x
Min
Standard
Max
Unit
Data type
Effective
0
33
87
–
Unsigned16
immed.
... defines the function of output terminal O0.x on the control module.
The function is entered from the ”List of output signals”.
Note:
refer to the index entry ”Terminals term. O0.x to O3.x” or ”List of the output signals”