6
6.8
Angular incremental encoder interface (X461, X462)
6-566
Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
When setting the angular incremental encoder interface as input for
incremental position reference values, the following parameters must
be observed:
P0032
External position reference value
P0890
Activates the angular incr. enc./encoder interface
P0891
Source, external position reference value
P0894
Angular incremental encoder input signal waveform
P0895
External position reference value – No. of increments
P0896
Ext. position reference value – No. of dimension
system grids
P0897
Inversion, external position reference value
For ”angular incremental encoder interface as input”, the following sig-
nal is available:
Input signal ”invert angular increm. encoder input” (from SW 3.5)
(refer under the index entry ”Input signal, digital ...”)
––> using an input terminal with function number 75
––> using the PROFIBUS control signal ”PosStw.7”
Parameter
overview
(refer to Chapter
A.1)
Input signal
(refer to Chapter
6.4)
6 Description of the Functions
01.99
! not 611ue !