SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
5.10.5
Example: Coupling 2 drives (master, slave drive)
The following example is based on the functionality of slave–to–slave
communications via PROFIBUS–DP. It shows the steps which are ne-
cessary, using SimoCom U, to parameterize the master and slave
drive.
We recommend the following sequence when parameterizing:
1. Parameterizing the master, e.g. SIMATIC S7
2. Parameterizing the master drive
3. Parameterizing the slave drive
Standard telegram 108 for the master drive (publisher)
Standard telegram 109 for the slave drive (subscriber)
Default
5 m, sufficient for the traversing range
An SFC14/15 cannot be used
P1009 = 4 ms
The steps when configuring an S7 are shown in the following Figs.:
The following data should be parameterized in the DP master (S7):
Configuration, master drive matching telegram 108
––> number of process data
– 4 words, PKW
– 10 words, actual values to the DP master (inconsistent)
– 10 words, setpoints from the DP master (inconsistent)
Fig. 5-35 Example, configuring the master drive for S7
General
information
Assumptions for
the example
Parameterizing DP
master
5 Communications via PROFIBUS DP
08.99
07.01
08.01