Net data (PKW and PZD area)
5-236
Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
Table 5-17
Status word MeldW
Reserved
Meld
W
ZSW
2
n
set
= n
act
Pulses enabled (from SW 3.1)
Spindle position reached (spindle position 2, from SW 5.1)
Power module current not limited (from SW 3.1)
Reserved
Position reached (spindle position 1, from SW 5.1)
Reserved
Bit
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
| M | < M
x
Ramp–up completed
| n
act
| < n
min
| n
act
| < n
x
DC link monitoring V
DC link
> V
x
Variable signaling function
Heatsink temperature pre–warning
Motor overtemperature pre–warning
Note:
From the perspective of SIMODRIVE 611 universal, status signals are output signals and are described
in Chapter 6.4.6.
Also refer in the index under ”Output signal, digital ...”).
The actually converted values of the 2 analog inputs of a drive are dis-
played using these status words.
ADU
1
ADU
2
Status word
Analog input
ADU1
X451
terminal 56.x/14.x
ADU2
X451
terminal 24.x/20.x
Note
The parameters available to parameterize the analog inputs are still
valid (refer to Chapter 6.6).
Data transfer format:
4000
hex
10 V
Update rate at which this signal is provided:
Clock–cycle synchronous PROFIBUS–DP
––> generally: DP clock cycle, sensed at instant in time T
i
non–clock–cycle synchronous PROFIBUS–DP
––> n–set mode:
Position controller clock cycle (P1009)
––> pos mode:
Interpolation clock cycle (P1010)
Status word
MeldW
Status word ADU1
ADU2
5 Communications via PROFIBUS DP
08.99
07.03