Settings at the PROFIBUS DP master
5-288
Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
Setting the PROFIBUS node address using the dia-
log box for the first start–up
1. Carry out the first commissioning (start–up) using the display and
operator unit and for the hardware configuration, do not enter the
configuration data up to the node address (refer to Chapter 4.4).
A1106 (power module code number)
do not set
...
(other parameters)
do not set
A0918 (PROFIBUS node address)
set
A0652 (write into the FEPROM) = 1
set
2. carry–out a POWER–ON RESET
3. ––> cyclic operation between
”DP slave 611U” <–––> PROFIBUS–DP master is possible
Note
The system can be commissioned and parameterized as follows:
With ”SimoCom U via PROFIBUS–DP” (from SW 3.1)
– Establish online operation (refer to Chapter 3.3.4)
– Carry–out the first or series commissioning (start–up) using
SimoCom U
(refer to Chapter 4.3.1 or 4.3.2, P0918 (PROFIBUS node
address) may not be overwritten).
Using ”read/write parameter ” via PKW section
The parameters of the ”DP slaves 611U” can be read/written into
via the PKW section from the PROFIBUS–DP master.