SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
1011
IM configuration, actual value sensing
Min
Standard
Max
Unit
Data type
Effective
0
0
F003
Hex
Unsigned16
PO
... allows the actual value sensing to be configured for an indirect measuring system.
Bit 0
Invert speed actual value
Bit 0 = 1
Inversion, speed actual value
Bit 0 = 0
No inversion
Bit 1
Encoder phase failure correction
Bit 1 = 1
Encoder phase failure correction
Bit 1 = 0
No encoder phase error compensation
Bit 2
Resolver resolution
Bit 2 = 1
Resolver resolution, 14 bits
Bit 2 = 0
Resolver resolution, 12 bits
Note:
14 bit resolver resolution can only be set with ”SIMODRIVE 611 universal HR”, otherwise error
759 is output.
Bit 12
Coarse position identification
Bit 12 = 2
Identify rough position
Bit 12 = 0
No coarse position identification
Note:
This bit has no significance for EnDat encoders.
For encoders without hall sensors and without C/D track (e. g. ERN 1387), the rotor position
identification replaces the coarse synchronization. The zero mark must still be adjusted (shift or
via P1017).
Bit 13
Fine position identification
Bit 13 = 1
Identify fine position
Bit 13 = 0
No fine position identification
Note:
This bit has no significance for EnDat encoders.
The rotor position identification replaces the coarse synchronization using Hall sensors or a C/D
track. The zero mark neither has to be present nor does it have to be adjusted.
If the rotor position identification does not offer satisfactory results, then the zero mark must be
adjusted.
Bit 14
Data transfer rate EnDat, bit 0
Bit 15
Transmission rate EnDat, Bit 1
Note:
Bits 14 and 15 are set as follows in the factory:
Bit 15, 14 = 00 ––> 100 kHz (standard)
Bit 15, 14 = 01 ––> 500 kHz (setting possible)
Bit 15, 14 = 10 ––> 1 MHz (setting, Siemens-internal)
Bit 15, 14 = 11 ––> 10 MHz (setting, Siemens-internal)
IM ––> Indirect measuring system (motor encoder)
refer to the index entry ”List of encoders”
1012
Function switch
Min
Standard
Max
Unit
Data type
Effective
0
2185
71F5
Hex
Unsigned16
immed. (ARM)
0
2105
71F5
Hex
Unsigned16
immed. (SRM SLM)
... allows the closed-loop control functions to be activated/de-activated.
Note:
Standard value for an activated PROFIBUS option module:
3185 (ARM)