SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
0410
Configuration, coupling which can be switched-in
(–> 3.3)
Min
Standard
Max
Unit
Data type
Effective
1
1
8
–
Unsigned16
PO
... defines the switch-on and type coupling.
1
Coupling via digital input signal, speed-synchronous
2
Coupling via digital input signal, position-synch P0412
3
Coupling via traversing program, speed-synchronous
4
Coupling via traversing program, position-synchP0412
5
Coupling via traversing program with queue functionality speed-synchronous
(being prepared)
6
Coupling via traversing program with queue functionality position synch P0412
(being prepared)
7
Coupling via digital input signal to absolute position of the master drive + P0412
(from SW 4.1)
8
Coupling via traversing program to absolute position of the master drive + P0412
(from SW 4.1)
Note:
For P0410 = 7 or 8, it is necessary to signal the absolute position P0400 of the master drive to
the slave drive using the input signal ”set setpoint, master drive”.
refer under the index entry ”axis couplings”
0412
Synchronous offset position
(–> 3.3)
Min
Standard
Max
Unit
Data type
Effective
–200000000
0
200000000
MSR
Integer32
immed.
... defines an offset between the slave drive and the synchronous position to the master drive.
Note:
If P0412 is changed, it becomes effective the next time that the coupling is switched-in.
refer under the index entry ”axis couplings”
0413
Offset, synchronous velocity
(–> 3.3)
Min
Standard
Max
Unit
Data type
Effective
1000
30000000
2000000000
MSR
Integer32
immed.
... defines with which additional velocity the slave drive corrects the following error, built-up dur-
ing the synchronization phase, and the synchronous offset position P0412.
Note:
refer under the index entry ”axis couplings”
0420
Pos. differ., meas. probe to the zero point, slave drive
(–> 3.5)
Min
Standard
Max
Unit
Data type
Effective
–200000000
0
200000000
MSR
Integer32
PO
... for couplings with queue functionality, specifies the clearance between the measuring probe
and the zero point of the slave drive.
Note:
refer under the index entry ”axis couplings”
0425:16 Coupling positions
(–> 3.3)
Min
Standard
Max
Unit
Data type
Effective
–
–
–
MSR
Integer32
RO
The following is valid for couplings without queue functionality:
The position of the master drive, at which the coupling was requested, is located in P0425:0.
For couplings with queue functionality (from SW 3.5) the following is valid:
The measured distances to the actual slave drive position are entered into P0425:16.
Note:
refer under the index entry ”axis couplings”
A Lists