Function–initiating and diagnostic parameters
4-131
Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
4.5
Function–initiating and diagnostic parameters
Table 4-2
Function–initiating parameters
Parameters
No.
Name
Min.
Standard
Max.
Units
Effective
0649
Delete parameters, drive A and B
(from SW 3.1)
0
0
1
–
PO
... all of the parameters can be deleted in the memory module FEPROM (user data). After these
parameters have been deleted, the status of the control board when it was first supplied is re–
established.
0
Standard value
1
All of the parameters should be deleted (establish the status when first supplied)
Procedure when deleting all parameters:
Switch–out the pulse and controller enable (e.g. via terminal 663, 65.A and 65.B)
Remove write protection (P0651 = 10
Hex
, only for the display and operator unit)
Activate that all parameters are deleted in the FEPROM (P0649 = 1)
Write into the FEPROM (P0652 = 1)
Carry–out HW POWER–ON RESET
After run–up, the board status when originally supplied is re–established.
0651
Read and write protection
0
0
10
hex
Immedi-
ately
This defines which parameters can be read (visible) or can be written into.
0
Parameters for standard commissioning (operator prompting) can be read
1
Parameters for standard commissioning (operating prompting) can be read and writ-
ten into
2
All parameters can be read
4
All parameters can be read and written into
(Exception: Motor data parameters cannot be written into)
8
Motor data parameters can be read and written into
10
All parameters (including motor data parameters) can be read and written into
Note:
Read and write protection is only of significance when parameterizing the display and operator
unit.
0652
Transfer into the FEPROM
0
0
1
–
Immedi-
ately
This means that parameter values can be transferred from the RAM into the FEPROM.
0 –> 1
The parameter values in the RAM are written into the FEPROM
The parameter is automatically set to 0 at the end of the data save operation.
1
Data is being saved – other parameters cannot be selected
Function–initiating
parameters
4 Commissioning
10.99