6
6.4
Input/output terminals of the control board
6-519
Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
Table 6-49
List of output signals, continued
Operating
mode
Signal name, description
PROFIBUS bit
pos
n–set
Fct. No.
Slave sign–of–life (from SW 3.1)
–
x
x
ZSW2.12
ZSW2.13
ZSW2.14
ZSW2.15
For the ”Motion Control with PROFIBUS–DP” function, these status signals are used as sign–of–life
(4–bit counter).
The sign–of–life counter is incremented from 1 to 15 and then starts again with the value 1.
It only starts to count, if:
The clock–cycle synchronous PROFIBUS operates in clock–cycle synchronism
For slave–to–slave communications, all of the links between the publisher and subscriber have been
established (from SW 4.1)
Note:
The ”Motion Control with PROFIBUS–DP” function is described in Chapter 5.8.
The ”slave–to–slave communications” function is described in Chapter 5.10 (from SW 4.1).
Suppress fault 608 active (from SW 3.1)
–
x
x
ZSW2.8
This output signal is the checkback signal when suppressing fault 608 is activated via the input signal
”suppress fault 608” (from SW 3.1)”.
1 signal
Suppressing fault 608 is active (speed controller output limited)
0 signal
Suppressing fault 608 is not active
Note:
Suppressing fault 608 (speed controller output limited) can be activated as follows:
–
via an input terminal with function number 26
–
via the PROFIBUS control signal STW2.8
Refer under the index entry ”Input signal – suppressing fault 608 (from SW 3.1)”
Traverse to fixed endstop active (from SW 3.3)
66
–
x
PosZsw.14
This output signal is used to display whether the ”travel to fixed endstop” function is active.
1 signal
Block with the FIXED ENDSTOP command is being processed
The ”travel to fixed endstop” function has been selected.
0 signal
No block with the FIXED ENDSTOP command is being processed
The ”travel to fixed endstop” function has been canceled.
Note:
The ”travel to fixed endstop” function is described in Chapter 6.12.
External block change (from SW 7.1)
67
–
x
AktSatz.14
This output signal is used to display whether the ”External block change” function is active.
1 signal
The ”external block change” function is selected.
0 signal
The ”external block change” function is canceled.
Note:
This output signal is an image of the input signal ”External block change” (Fct. No. 67 and STW1.13).
When the edge of this output signal changes, this indicates that a block change has taken place, i.e.
especially in the MDI mode, a new MDI block may now be entered via PZD and/or default block (refer
to Chapter 6.2.12).
6 Description of the Functions
01.99
! 611ue diff !
08.01
02.03