7
7.3
List of faults and warnings
7-711
Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
884
PZD configuring: Double word signal number in
P0916:\%u ivalid
Cause
For signals with double words (length = 32 bits), the corresponding sig-
nal identifier must be configured twice for adjacent process data. The
following subparameter must therefore also be parameterized with the
same signal number.
Remedy
Correct P0916:17
Acknowledgement not required
Stop response
STOP VII
885
P1261 greater than 100.0 % not permissible
Cause
P1261 greater than 100.0 % is not permissible for permanent-magnet
synchronous motors with field weakening (PE spindle, P1015 = 1). It is
internally limited to 100.0 %.
Remedy
Set P1261 to max. 100.0 %.
Acknowledgement not required
Stop response
STOP VII
886
Pre-tensioning torque greater than 16x rated torque
Cause
The parameterized pre-tensioning torque (P1493) is greater than 16x
the standstill torque (SRM), rated motor torque (ARM) and standstill
force (SLM) of the motor.
Note: refer to the index entry ”Limits”
Remedy
Reduce pre-tensioning torque (P1493)
Acknowledgement not required
Stop response
STOP VII
889
Fixed endstop, axis has not reached the clamping
torque
Cause
The axis has reached the fixed endstop, but was not able to establish
the programmed clamping torque.
Remedy
Check the parameters for the limits.
Acknowledgement not required
Stop response
STOP VII
890
Acceleration – deceleration override incorrect
Cause
The acceleratino override or the deceleration override is not in the
range from 1% to 100%.
if the value > 100%, then it is limited to 100%.
If the value < 1%, then limited to 1%.
The traversing block is not interrupted.
Remedy
Check the programming of the acceleration override and deceleration
override.
Acknowledgement not required
Stop response
STOP VII
7 Fault Handling/Diagnostics
01.99
04.05