2.1
Installing/removing control boards and modules
2-60
Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
2.1
Installing/removing control boards and modules
!
Warning
It is only permissible to install/remove a control board or an option
module when the system is in a no–voltage condition (powered down).
If boards or option modules are inserted or withdrawn under voltage,
this can result in data loss or destruction of components.
Note
The screws retaining electrical connections at the modules must be
tightened with the following torque:
Screw size
––> tightening torque
M3
––>
0.5 Nm (for electrical connections)
M3
––>
0.8 Nm (for mechanical connections)
M4
––>
1.8 Nm
M5
––>
3.0 Nm
Tolerance
––>
0/+30 %
After transport, the screws should be tightened!
The following points must be observed when installing the
”SIMODRIVE 611 universal” control board into the power module
(refer to Fig. 2-1):
!
Warning
The ESDS measures must be observed when installing/removing the
control board.
1. Ensure that the power module is in a no–voltage condition.
2. Check that the memory module is inserted and locked into place in
the control board.
If it is not inserted, then refer to the point ”installing/removing the
memory module”.
3. Insert the control board in the power module.
4. Tighten up the screws retaining the board
(2 screws on the front panel, max. torque= 0.8 Nm).
5. Connect–up the front panel of the board corresponding to the con-
nection diagram (refer to Chapter 2.3.1).
The mating connectors are inserted at the appropriate interface.