SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
830
PROFIBUS: Illegal configuration received. Reason: \%u
Cause
An illegal configuration frame was received via PROFIBUS. Cyclic data
transfer cannot start.
Reasons:
1 = In the master, more axes are configured than are physically
present in the power module.
2 = The number of the axes configured in the master is not equal to
the number axes where the PROFIBUS DP option module is
switched active via P0875. Note: Communications with axis B are
not automatically de-activated even when switching axis B into a
passive state.
3 = Configuration incomplete (too short) for one of the PPL types
(only for vor P875 = 2).
4 = No PPO type detected (only for P875 = 2).
5 = Length calculation different between firmware and option module.
6 = For active data exchange, a new configuration was received with
different length.
7 = Configuration contained unknown S7 ID.
19 = More PZD’s have been configured than the maximum permissible.
20 = The configurtion contains an unknown special character (only axis
separators are permitted).
22 = Target offset of slave-to-slave communications access exceeds
the maximum number of PZDs
28 = Number of slave-to-slave communication IDs differs from the
number of accesses in the parameterizing telegram.
29 = Setpoint PZDs are not uniformly supplied by the master or slave
(drive) publisher.
30 = The permitted maximum length of the configuration telegram for
the option module has been exceeded.
Remedy
Check the bus configuring at the master and if required correct.
If required, using P875, activate the option module PROFIBUS-DP,
which are previously configured in the PROFIBUS Master for the num-
ber of axes involved.
Acknowledgement not required
Stop response
STOP VII