1
1.4
”SIMODRIVE 611 universal E” control board
1-56
Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
Table 1-8
Differences with respect to ”SIMODRIVE 611 universal”, continued
Differ-
ence
This should be observed for
SIMODRIVE 611 universal E
SIMODRIVE
Differ-
ence
This should be observed for
SIMODRIVE 611 universal E
611 universal E
611 universal
Software
release
SW 1.1
SW 2.1
SW 2.4
SW 3.x
SW 4.1
SW 5.1
SW 6.1
no
no
no
SW 3.x
SW 4.1
SW 5.1
SW 6.1
Software release 3.1 is the first software release which
is used for both modules.
The following applies for ”SIMODRIVE 611 universal E”:
Software from SW 3.1 onwards must be used.
Module
type
The module is identified using
P0870 (module type)
P0870 = 0004
hex
––> it involves a ”SIMODRIVE 611 universal E” control
board, 2–axes for encoders with sin/cos 1 Vpp
Analog
inputs
T. 56.x/14.x
T. 24.x/20.x
no
no
The information in Chapter 6.6 is of no significance.
Digital in-
puts:
Term. I0.x
Term. I1.x
Term. I2.x
Term. I3.x
Term. I0.x
Term. I1.x
no
no
Effective parameters are:
–
P0660 (function, input terminal I0.x)
–
P0661 (function, input terminal I1.x)
P0662 and P0663 are ineffective
Digital
outputs:
Term. O0.x
Term. O1.x
Term. O2.x
Term. O3.x
Term. O0.x
Term. O1.x
no
no
Effective parameters are:
–
P0680 (signal function, output terminal O0.x)
–
P0681 (signal function, output terminal O1.x)
P0682 and P0683 are ineffective
Optional
TERMI-
NAL
module
Yes,
can be used
No,
cannot be used
P0664 to P0671 (function, input terminal I4 to I11)
and
P0684 to P0691 (signaling function, output terminal O4
to O11)
are of no significance
Optional
TERMI-
NAL
module
PROFIBUS
DP1
PROFI-
BUS–DP2
PROFI-
BUS–DP3
no
no
PROFI-
BUS–DP3
P0872 = 4
––> The following option module was detected:
Optional PROFIBUS–DP3 module (from SW 3.1)
with PROFIBUS–ASIC DPC31 with PLL
Order No. (MLFB): 6SN1114–0NB01–0AA0
Serial in-
terface
RS232
RS485
(indepen-
dent of the
hardware)
RS232
no
Permissible settings
–
P0801 = 0 (RS232 interface, standard)
P0801 = 1 is interpreted just like P0801 = 0
P0802 and P0803 are of no significance
1 Product Overview
01.99
! not 611u !
05.00