6
6.4
Input/output terminals of the control board
6-474
Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
6.4.2
Freely–parameterizable digital input terminals
There are 4 freely parameterizable input terminals for every axis.
A terminal is parameterized by entering the appropriate required func-
tion number into the assigned parameter.
Which function numbers are available? ––> Refer to Chapter 6.4.3
Note
Rules when assigning input terminals a multiple number of times
The terminals are evaluated in the following sequence:
I0.x – I1.x – I2.x – I3.x – I4 – I5 – ... – I11
If a function is assigned a multiple number of times to an input
terminal, influence is only possible using the ”last” terminal
assigned this particular function.
Rule regarding hardware terminal and PROFIBUS signal
The hardware terminal has priority over the PROFIBUS signal, this
means that a signal via a terminal always has priority over the
”same” PROFIBUS signal.
Notice
The terminals may only be parameterized when the drive pulses are
canceled.
If terminal functions are activated, however, are not connected–up,
then the ”0” signal is effective.
There is the following assignment between terminals, drives and para-
meters:
Table 6-43
Overview of the freely–parameterizable input terminals
Terminals
Parameters
Drive A
Drive B
No.
Name
Min.
Standard
Max.
Units
Ef-
fec-
tive
I0.A
X451.7
I0.B
X452.7
0660
Function, in-
put terminal
I0.x
0
0 (SRM, SLM)
35 (ARM)
82
–
Im-
medi-
ately
I1.A
X451.8
I1.B
X452.8
0661
Function, in-
put terminal
I1.x
0
0 (SRM, SLM)
7 (ARM)
82
–
Im-
medi-
ately
Description
Overview of the
terminals and
parameters
6 Description of the Functions
01.99
! 611ue diff !
04.99