6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 1198 -
(iii)
Qual_validity
Qual_validity (61850 signal: No. 301001 3110041005) is a signal provided for a common quality
information. It can be useful if some ‘q’ attributes (it’s defined in Quality type) should belong
to a common quality. Both severe and non-severe errors are included; therefore, that signal
value will be changed whenever errors (including alarm and warning incidents) are detected.
In this quality signal, the Detail quality information—defined in the standard—is not set at
all.
Figure 11.3-32 Structure of Qual_validity signal
Note:
If non-severe incidents—such as Minor, Alarm, or Warning error are detected in
the automatic supervisions, the IEC61850 interrupts the Qual_Validity as
‘questionable (i.e., the string of Qual_Validity is 1100000000000)’.
If severe incidents—such as Serious or Serious (comm) error are detect, the
IEC61850 interrupts the Qual_Validity as ‘invalid (i.e., it is 0100000000000)’.
If non-severe and sever incidents occur at the same time, the output of the
Qual_Validiy is ‘invalid (i.e., it is 0100000000000)’.
The test mode will be expressed if the Qual_Validiy has a test-bit (that is,
‘0000000000010’).
The outputs of MINR_ERR and SERI_ERR come from the MNT_LOGIC function
block (see Chapter
Automatic supervision: Supervision of task operation).
Test function block can output the Test Mode signal (see Chapter
Commissioning
and maintenance: Test operations).
≥1
0 0 0
Kinds of
Validit
y
ov
e
rflow
outOfRa
nge
bad
Re
fer
en
ce
oscillator
y
failure
o
ldDat
a
inc
o
ns
istent
inaccu
ra
te
so
u
rce
test
operator
blo
cked
Qual_Validity
0 0 0
0 0 0
0 0
Detail quality
SERI_ERR
Test Mode
220001 3110111001
220001 3110121001
201301 3100001190
301001 3110041005
MINR_ERR
Kinds of Value
Validity
Good 00(default)
Invalid 01
Questionable 11
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......