6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 1326 -
1 Time counter, precision timer
1 PC (not essential)
Relay settings
Before starting the tests, it must be specified whether the tests will use the user’s settings or
the default settings.
Visual inspection
After unpacking the product, check for any damage to the IED case. If there is any damage,
the internal module might also have been affected. Contact the vendor.
Relay ratings
Check that the items described on the nameplate on the front of the IED conform to the user’s
specification. The items are: relay type and model, AC voltage, current and frequency ratings,
and auxiliary DC supply voltage rating.
Local PC
To examine the IED with a PC locally, connect the PC with the IED using a USB cable. The
GR-TIEMS software is required to install in the PC.
During commissioning and maintenance, check wire connection and observe relay output
signals. The user can see the signals whether the relay operations are appropriate or not.
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......