6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 451 -
ASEQ
User’s PLC
logic
SPOS
PLC connection point
DPOS
User’s PLC
logic
PLC monitoring point
Figure 3.5-2 Example of user-preferred control scheme using PLC user logic
Note: The user-preferred control scheme implemented by users can only be operated in
the DIR mode.
3.5.4
Signal for Local/Remote control
Note: The following references are used in the column “M/O” in Table 3.5-3 and Table
“O” means the signal is optional.
“M” means the user should map/set/configure the signal; otherwise, the user
may experience an operational failure if the default settings are used.
“N/A” means that the user cannot change the state of the signal.
Table 3.5-3 PLC connection point (Input point for LOCRMT)
Signal Number
Signal Name
Description
M/O
240001 31000A1735
L/R CHG
[L/R] key “push”
N/A
530001 800901EDE0
LRSW01_PLC_SGN01
Disable condition by PLC
O
530001 800901EDE1
LRSW01_PLC_SGN02
User configurable condition by PLC
O
Table 3.5-4 Mapping points for LOCRMT
Signal Number
Signal Name
Description
M/O
530001 3009011008
LRSW01_LR_ORCAT
Mapping data for “originator” in IEC61850
N/A
530001 6A09011009
LRSW01_LR_ORIDENT
Mapping data for “originator” in IEC61850
N/A
Table 3.5-5 PLC monitoring point (LOCRMT)
Signal Number
Signal Name
Description
530001 3109001001
LRSW01_LR_ST
Local(T) / Remote(F) status (single bit expression)
530001 3009011001
LRSW01_LR_ST_RMT
Local(0x40) / Remote(0x80) status (double bit expression)
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......