6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 544 -
4.1.6
Setting
SPOS01 (FunctionID:510001)
Setting items
Range
Unit
Contents
Default
Note
Commo n items SPOS-NELD
0 - 99
- Number of Event lock detect time
10
SPOS-TELD
1 - 99
s Timer of detect event lock
10
SPOS-TELR
1 - 99
s Timer of recovery from event lock
10
SPOS01-EN
Off / On
- SPOS01 switch for Device01
Off
DEV01 items SPOS01-DEVNAME
[Preferred text]
- item name of Dev1
SPOS_Dev1
!
SPOS01-OFFNAME
[Preferred text]
- state name of state(off)
Off
!
SPOS01-ONNAME
[Preferred text]
- state name of state(on)
On
!
SPOS01-NOPSG
[Preferred Signal]
- Normally Open Signal of Dev1
Not Assigned
SPOS01-SPPEN
Off / On
- Automatic event suppression function
Off
SPOS01-CTREN
Off / On
- control mode (control enable)
Off
SPOS01-CTRMENU
Off / On
- control by MENU enable
Off
SPOS01-CTRAHMI
DIR / SBO
- control action(Direct or SBO)by HMI
SBO
SPOS01-SLBORD
[Preferred Signal]
- select binary output read data(DataID)
5100018501011F76
SPOS01-OEXBORD
[Preferred Signal]
-
on direction execute binary output read
data(DataID)
Not Assigned
SPOS01-FEXBORD
[Preferred Signal]
-
off direction execute binary output read
data(DataID)
Not Assigned
SPOS01-OFEXBORD
[Preferred Signal]
-
on/off direction execute binary output read
data(DataID)
Not Assigned
SPOS01-LGCTRCON
FixedLogic /
PLC
- Change logic about control condition
FixedLogic
SPOS01-LGSLFFCT
FixedLogic /
PLC
- Change logic about select fail factor
FixedLogic
SPOS01-LGEXFFCT
FixedLogic /
PLC
-
Change logic about execute command fail
factor
FixedLogic
SPOS01-LGFEXOT
FixedLogic /
PLC
-
Change logic about off direction execute
output
FixedLogic
SPOS01-LGCNFFCT
FixedLogic /
PLC
- Change logic about cancel command fail factor
FixedLogic
SPOS01-PLSM
Fix / Var / Latch - pulse mode
Var
SPOS01-CPW
0.1 - 50.0
s control pulse width
1.0
SPOS01-RST
1.0 - 100.0
s response check timer
30.0
SPOS01-APBD
Process / Bay
- status change origin
Process
!Note: The user can enter a preferred setting name using GR-TIEMS.
Note: The SPOS function is available for a 2
nd
Device and other devices. We have
omitted the others because their setting tables are the same as the 1
st
device table
with the exception of the device number.
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......