Setting list
OV(Function ID: 460101)
Setting items
Range
Unit
Contents
Default
Note
1A rating
5A rating
1A
5A
OV1-EN
Off / On
- OV1 protection scheme switch
Off
OV2-EN
Off / On
- OV2 protection scheme switch
Off
OV1
OV1-Timer
DT / IDMT / Original - OV1 delay type
DT
DT
OV1
1.0 - 220.0
V OV1 threshold
120.0
TOV1
0.00 - 300.00
s OV1 operating delay time (in DT mode)
1.00
OV1-DPR
10 - 100
% OV1 drop-out/pick-up ratio
100
IDMT
OV1
1.0 - 220.0
V OV1 threshold
120.0
OV1-DPR
10 - 100
% OV1 drop-out/pick-up ratio
100
OV1-TMS
0.010 - 100.000
- OV1 time multiplier (in IDMT mode)
1.000
TOV1R
0.0 - 300.0
s OV1 definite time reset delay
0.0
ORG
OV1
1.0 - 220.0
V OV1 threshold
120.0
OV1-DPR
10 - 100
% OV1 drop-out/pick-up ratio
100
OV1-TMS
0.010 - 100.000
- OV1 time multiplier (in ORG mode)
1.000
TOV1R
0.0 - 300.0
s OV1 definite time reset delay
0.0
OV1-k
0.00000 - 500.00000 - OV1 user original curve coefficient
0.00000
OV1-a
0.00000 - 10.00000
- OV1 user original curve coefficient
0.00000
OV1-c
0.00000 - 10.00000
- OV1 user original curve coefficient
0.00000
Output OV1-VTFBlk
Non / Block
- OV1 operation block by VTF
Non
OV1-UseFor
Trip / Alarm
- OV1 used for trip or alarm
Trip
OV2
OV2-Timer
DT / IDMT / Original - OV2 delay type
DT
DT
OV2
1.0 - 220.0
V OV2 threshold
120.0
TOV2
0.00 - 300.00
s OV2 operating delay time (in DT mode)
1.00
OV2-DPR
10 - 100
% OV2 drop-out/pick-up ratio
100
IDMT
OV2
1.0 - 220.0
V OV2 threshold
120.0
OV2-DPR
10 - 100
% OV2 drop-out/pick-up ratio
100
OV2-TMS
0.010 - 100.000
- OV2 time multiplier (in IDMT mode)
1.000
TOV2R
0.0 - 300.0
s OV2 definite time reset delay
0.0
ORG
OV2
1.0 - 220.0
V OV2 threshold
120.0
OV2-DPR
10 - 100
% OV2 drop-out/pick-up ratio
100
OV2-TMS
0.010 - 100.000
- OV2 time multiplier (in ORG mode)
1.000
TOV2R
0.0 - 300.0
s OV2 definite time reset delay
0.0
OV2-k
0.00000 - 500.00000 - OV2 user original curve coefficient
0.00000
OV2-a
0.00000 - 10.00000
- OV2 user original curve coefficient
0.00000
OV2-c
0.00000 - 10.00000
- OV2 user original curve coefficient
0.00000
Output OV2-VTFBlk
Non / Block
- OV2 operation block by VTF
Non
OV2-UseFor
Trip / Alarm
- OV2 used for trip or alarm
Trip
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......