6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 886 -
device, but a 2
nd
and other devices are also provided in the ASEQ function. We
have omitted the Element IDs and their names for the other devices to improve
readability. Use the rule described below when the user wishes to obtain the
Element IDs and their names for the other devices.
Rule: The same types of signal monitoring points are provided in every device;
hence, the user can find the same ones for all of the other devices. For
example, when the user wishes to find the “ASEQ01_EC_LCD” point for
the 2
nd
device, use the description of “ASEQ02_EC_LCD” in place of
“ASEQ01_EC_LCD”. The user can obtain the ID value of
“ASEQ02_EC_LCD” by using the following steps:
Step 1
Find the element ID for ASEQ01_EC_LCD (i.e.,
“800D011D58”)
Step 2
Identify the number at the fifth digit from the ID. (i.e., “1”)
Step 3
Choose a new device number. (i.e., pick the number “2” for
the 2
nd
device)
Step 4
Replace the number that occurs at the fifth digit with the
new device number. (i.e., get new ID “800D021D58” of
“ASEQ02_EC_LCD”) The ID is expressed in hexadecimal
notation. Thus, the user must change the device number
from decimal notation to hexadecimal notation.
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......