6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 1182 -
Edit GOOSE Control Block
GOOSE control block is used to exchange information between IEDs. GOOSE
messages are used for interlock operation between IEDs in order to protect the
electrical system. GGIO1 is used for sending high-speed GOOSE messages. The
DataID assigned to GGIO1 is sent within 3ms.
If the user wishes to assign the DataID for GOOSE operation, follow the steps
below:
1.
Click GGIO1 and select Ind1 as shown in Figure 11.3-19.
2.
Drag and Drop the required signals to be sent by GOOSE.
Note: The user can assign any signal to GGIO1->Ind1~16 for high-speed GOOSE, as
required.
Drop
Drag
Figure 11.3-19 Signal mapping for high speed GOOSE
As shown in the above figure, signals are assigned to “System/GGIO1$Ind1”. The
user can assign signals to other GGIOs (for example, GGIO2, GGIO3 and so on)
which are not meant for high-speed GOOSE operation.