6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 1301 -
reproduce a pseudo-operation condition.
GOOSE sending block (GOSNDBLK)
This function is used for selecting or disabling the GOOSE sending
information in Test mode. This function is used when there is a conflict in
communication with another active IED while sending a GOOSE signal.
GOOSE receiving block (GOSUBBLK)
This function is used for receiving or rejecting GOOSE subscription
information from another IED in Test mode. This function is used for testing
in case of bad reception (For example, Validation of Interlock determination).
The user can simulate a bad reception condition passively by using two
GOOSE Sending Blocks.
Note: The user may perform bad reception tests from a remote terminal using the
GOSNDBLK function. However, carrying out the GOSNDBLK function at a
remote terminal may influence the overall operation of other IEDs, because
communication packets will not be received from the remote terminal. In order to
avoid that the user can simulate bad reception tests for a particular IED using the
GOSUBBLK function. As a result, testing will only affect the particular IED
under test i.e. all other terminals will not be influenced by the tests.
Function test screen
:
Function test screen is provided for testing; the use can
program test operations, which can be implemented in protection and control
functions. Figure 12.8-4 exemplifies the Test screen. Automatic supervision
will stop when the user sets
Off
for A.M.F (for more information about the
automatic supervision, see
Chapter Automatic supervision
).
Figure 12.8-4 Function test menu (an example)
Binary input test screen
:
The user can have a virtual signal to a binary input
circuit using the binary input test screen. Figure 12.8-5 shows an example;
the user can select IO#1 or IO#3. (Actually, the content displayed will differ
depending upon the binary IO module inserted. Refer to Chapter
Technical
Function Test
10:48 1/65
A.M.F. +
On
BU1_Exclusion +
Off
BU2_Exclusion +
Off
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......