6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 537 -
Figure 4.1-38 shows a setting example for an improper setting of the 43SW scheme. The
settings are implemented incorrectly, as shown in Table 4.1-23. BO1-RB is not chosen,
instead BO1 is actually chosen. In this case, the setting [
SPOS01-SLBORD
] is meaningless;
hence, the issue of a select command is blocked.
Table 4.1-23 Erroneous setting example for contact health check
Example #2
Health check setting in example #2
“SPOS01_SL_BO_FLG” is connected to “BO1” at IO#1
200B01 8002001112(BO1) set for [
SPOS01-SLBORD
]
NG
“SPOS01_OEX_BO_CSF” is connected to “BO2” at IO#1
200B01 8102011113(BO2-RB) set for [
SPOS01-OEXBORD
] OK
“SPOS01_FEX_BO_CSF” is connected to “BO3” at IO#1
200B01 8202021113 (BO3-RB) set for [
SPOS01-FEXBORD
] OK
“SPOS01_SL_BO_FLG”
(510001
_
8501011F76)
SW1 driven with
BO1at IO_SLOT1
BO1
BIO module
“BO1” (not BO1-RB)
mistakenly chosen with
“200B01
_
8002001112
”
BO2
“SPOS01_OEX_BO”
(510001
_
8201011DD3)
“BO2-RB” designated with
“200B01
_
8102011113
”
BO3
“SPOS01_FEX_BO”
(510001
_
8101011DD0)
“BO3-RB” designated with
“200B01
_
8202021113
”
SW2 driven with
BO2 at IO_SLOT1
SW3 driven with
BO3 at IO_SLOT1
Remote/Local-end
Plus (+)
SW 3
SW 2
SW 1
Minus (
−)
43SW
On
Command
Off
Command
Select
Command
ON/OFF
Operate-On
command
Operate-Off
command
Figure 4.1-38 Contact health check setting and 43SW diagram for example #2
Setting for extra contact health check (special setting, example #3)
Figure 4.1-39 shows an additional setting example for the 43SW scheme; one of the settings is
made hypothetically. That is, the point “SPOS01_SL_BO_FLG” is actually chosen for the
setting [
SPOS01-SLBORD
]; i.e. BO1-RB is not chosen for this selection. This special example
can issue a select command; which is called “operated by internal select function”. The user
does not need to consider of a BO circuit for a select command, when there are no BO circuits
available.
Table 4.1-24 Extra setting example for contact health check
Example #3
Setting for example #3
“SPOS01_SL_BO_FLG” is not connected to any “BO”
“SPOS01_SL_BO_FLG” set for [
SPOS01-SLBORD
]
OK
“SPOS01_OEX_BO_CSF” is connected to “BO2” at IO#1
200B01 8102011113(BO2-RB) set for [
SPOS01-OEXBORD
] OK
“SPOS01_FEX_BO_CSF” is connected to “BO3” at IO#1
200B01 8202021113 (BO3-RB) set for [
SPOS01-FEXBORD
] OK
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......