6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 1175 -
(iii)
IEC 61850 configuration files
Substation configuration language (SCL) files are generated by the configuration in the IEC
61850 protocol. The SCL files are used to exchange the configuration data in different
manufacture tools. Two types of files are used for exchanging data in Table 11.3-5.
Table 11.3-5 Types of SCL files
SCL file
Description
.ICD
IED Capability Description
This file describes the capabilities of an IED. It contains the
communication data and function of LN in an IED.
.CID
Configured IED Description
Every device configured for IEC 61850 in the GR-TIEMS tool
generates a CID file. This file is then written to the IED. This
file contains configuration information of the IED to which it is
connected.
Exporting and Importing CID/ICD file
The user can export or / import a CID/ICD file as a CSV file. The user can edit
the exported CSV file using the MS-EXCEL®; the user can import the edited CSV
file back to the GR-TIEMS. Figure 11.3-10 shows the options available to
import/export CID/ICD file. The user can either click the icons on the menu bar
or select the required option form the File menu drop down list.
Import CID/ICD
Export CID
Export ICD
Figure 11.3-10 Export / Import of CID / ICD file
Manage third party CID file
The GR-TIEMS can have third party CID file. In the project tree of the GR-TIEMS,
the user can use the device information for creating a third Party IED. To
configure dataset, RCB, GCB, GOOSE publish and GOOSE subscribe settings
and so on, the data attributes are used after the creation of the data.
Mapping application data in IEC 61850
For any IED, the IEC61850 configuration* is available by default. The user
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......