Output signal for monitoring
The user can monitor a “Select success” signal at the output point “S4301_OSL_CSF”, when
the SOFTSW1 function determines that the received “Remote-ON-Control” signal is true. If
the SOFTSW1 function determines that the “Remote-ON-Control” is not true, the SOFTSW1
function returns to the “Wait for a command” stage.
(ii)
Receiving “select command for Off operation” from the remote end
Input point required mapping
Figure 4.3-7 shows the logic when a “Select command (Remote-OFF-Control)” signal is applied
at the SOFTSW1 function. The input-point “S4301_CONTROL_REQ” is used for the reception
of the select command (Remote-OFF-Control).
“S4301_FSD_CSF”
(522001
_
8D0A041F45)
SOFTSW1 function (Function ID:
522001)
S4301_CONTROL_REQ
Command
“Remote-Off-Control”
Either
“SBO mode” or “DIR mode”
(e.g.,
“ctlmodel” in IEC61850
*
)
In SBO operate
In DIR operate
Select
“Failed”
522001
_
700A046D08
For monitoring
Input
Output
Select logic in SOFTSW1
0.1s
0
t
0.6s
0
t
&
&
&
Select
“success”
“Automatic sequence control function (AQEQ)
§
” in progress
ASEQ_MULTI_SEL
Select condition
‡
1
≥
Select command
Operate command
For SBO operation
For DIR operation
To
“Wait for a command”
Figure 4.3-7 Select logic for ‘OFF’ operation from remote end in SOFTSW1
†
†Note: To identify the input and output points of the other SOFTSW logics, see Table
‡Note: “Select condition” signal is provided in Figure 4.3-12.
Output signal for monitoring
The SOFTSW1 function, in Figure 4.3-7, can issue a “Select success” signal at output point
“S4301_FSL_CSF” when the SOFTSW1 function determines that the input signal “Select
command (Remote-OFF-Control)” is true. If the SOFTSW1 function determines that the
“Remote-OFF-Control” is not true, the SOFTSW1 function returns to the “Wait for a command”
stage.
(iii)
Receiving “Selection command for On operation” from the front
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......