6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 1407 -
(PIXIT Ed.1&Ed.2)
12.
PIXIT FOR GOOSE SUBSCRIBE MODEL (continued)
ID
Ed
Description
Value / Clarification
Gs10 1,2 Max number of dataset members
64
<additional items>
1,2
Are subscribed GOOSE with ndsCom=T
Accepted.
GOOSE subscribe quality
information will become
QUESTIONABLE
|
INACCURATE (=1100 0000 0100 0).
GOOSE status change is ignored.
The behavior can be changed by
modifying PLC logic.
13.
PIXIT for GOOSE performance
ID
Ed
Description
Value / Clarification
Gf1 1,2
Performance class
P1(Ed.2) for
System/LLN0$GO$goST
P3(Ed.2) for all other GOOSE
Gf2 1,2
GOOSE ping-pong processing method
Scan cycle based
Gf3 1,2
Application logic scan cycle (ms)
Max. …. 200ms
Min. 1.38ms in 60Hz
Gf4
1
Maximum number of data attributes in
GOOSE dataset (value and quality has to be
counted as separate attributes)
The dataset for
System/LLN0$GO$goST is fixed,
and it contains 32 data attributes.
All other dataset for GOOSE can be
configurable, and there is no
particular limitation about the
maximum number of data
attributes. However, the dataset
definition shares the same dynamic
memory area as other data model
definitions such as LN, RCB, etc., so
it is affected by them.
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......