3.7.2
Select logics for SBO/DIR modes
The user should set scheme switch [
GCNT01-EN
] to
On
prior to counting.
(i)
Receiving “Select command Reset” from the remote-end
Figure 3.7-5 outlines the reception of the Select command ‘Reset’ from the remote-end.
Signal
reception
IEC61850
Select command Reset from the remote-end
Signal output
Select
decision
Success
Failed
Select logic
Select stage
Cancel logic
Wait for a next command
Cancel command
Wait for a command
Operate logic
Operate command
Cancel logic
Operate logic
Figure 3.7-5 Outline of Select command ‘Reset’
Input point required mapping
Figure 3.7-6 shows the select logic when a “Select command Reset (Remote-Reset-Control)”
signal is applied to the GCNT01 function. The logic has an input-point “GCNT01_CMM_REQ”
for the reception of the select command. That is, the input-point must be mapped for IEC61850
communication. The function will fail to operate if mapping is not performed correctly. We will
discuss how to map the input-points for IEC61850 communication in section 3.7.5.
Output signal to BO
The GCNT01 function can issue a “Complete” signal at the output point
“GCNT01_SLD_CSCN”, when the GCNT01 function determines that the input signal
“Remote-Reset-Control” is true. If the GCNT01 function determines that the “Remote-Reset-
Control” is not true, the GCNTS01 function returns to the “Wait for a command” stage.
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......