6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 819 -
§§Note: The signal “TPOS01-PIEX-BO” is issued when
Fixlogic
is set for the scheme
switch [
TPOS01-LGP1EXOT
]. The “Operate completed” signal can also be issued
from the logic programmed by the user in place of the logic shown in Figure
4.9-26. The user-programmed logic is connected internally to the “operate
completed”, hence this signal is now generated by the user-programmed logic at
connection point#2 “User configurable condition”. That is, set the scheme switch
[
TPOS01-LGP1EXOT
] to
PLC
and use “TPOS01IN_TMP_38”.
Output signal to BO
The TPOS01 function, in Figure 4.9-33, can issue an “Operate” signal at the output point
“TPOS01_P1EX_BO”, when the TPOS01 function determines that the “Local-P1-Control”
signal is true.
(v)
Receiving “operate command P2-control” from the local-end
Figure 4.9-34 depicts the reception of the operate command ‘P2-control’ from the local-end.
Signal reception from
the front panel
P2 control from the local-end
Do nothing
Operation
decision
Success
Failed
Operate logic
P1 control from the remote-end
P2 control from the remote-end
P3 control from the remote end
P1 control from the local-end
P1 control by the PLC function
P3 control from the local-end
P2 control by the PLC function
Wait for a command
P2 control from the local-end
P3 control by the PLC function
Select logics
Signal output
P3 control from the remote end
P1 control from the local-end
P1 control from the remote-end
P2 control from the remote-end
P3 control from the local-end
P1 control by the PLC function
P2 control by the PLC function
P3 control by the PLC function
Wait for a next command
Figure 4.9-34 Outline of Operate command ‘P2-control’
Input signal generated at the local-end.
Figure 4.9-35 illustrates the operate logic when an “Operation command P2 (Local-P2-Control)”
signal is applied to the TPOS01 function. The input signal is provided when “P2-control” is
keyed on the IED front panel.
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......