6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 514 -
is true. Another “Operation failed” signal is issued at the monitoring point “SPOS01_CC_FS”
if the SPOS01 function is able to determine that the “Remote-cancel” signal is not true.
(ii)
Receiving “Cancel” from the local-end
Figure 4.1-16 outlines the reception of the cancel command from the local end.
Press cancel
command
Cancel from the front panel
Do nothing
Cancel
decision
Success
Failed
Cancel logic
Wait for a command
Operate logic
Operate command
Operate logic
Select logics
Selecting Off from remote-end
Selecting On from remote-end
Selecting Off from front panel
Selecting On from front panel
Selecting On by the PLC function
Selecting Off by the PLC function
Cancel from the remote end
Wait for a next command
Figure 4.1-16 Outline of ‘cancel’ command from the local-end
Input signal generated at the local-end
Figure 4.1-17 depicts the cancel logic when a “Cancel command (Local-cancel)” signal is applied
to the SPOS01 function. The signal is generated when the “Cancel” key is pressed on the IED
front panel; the user is not required to take account of mapping. When the logic receives the
“Local-cancel” signal, the logic is able to output a result signal; provided that the “cancel
condition” checking is satisfied.
SPOS01 function (Function ID:
510001)
“SPOS01_ CC_SS” (510001
_
8601011E95)
Cancel command
510001 7001016D08
Input
Output
Cancel logic in SPOS01
Cancel condition
†
&
&
Successes to cancel
Operation Failed
“SPOS01_CC_FS” (510001
_
8701011E96)
Command
“Local-cancel”
“Do nothing”
To
“Wait for a command”
Figure 4.1-17 ‘Cancel’ from the front panel
Output signal to BO
The SPOS01 function, illustrated in Figure 4.1-17, is able to issue a “Select to cancel” signal
at the monitoring point “SPOS01_CC_SS”, when the SPOS01 function determines that the
“Local-Cancel” signal is true.
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......