6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 472 -
(ii)
Select condition
Figure 3.7-8 shows the select condition logic in the GCNT01 function. The GCNT01 function
checks the condition for the select command using the signal “S4301_STATE” and other signals.
When resetting the counter is performed from the “Statics sub-menu” in the HMI operation†,
the user should set
On
for scheme switch [
GCNT01-HMI
].
†Note: The HMI operation is discussed in
Chapter User interface: Monitoring sub-menu.
Select condition
GCNT01 function (Function ID: 540001)
To select logic
From Control hierarchy *5
From CMNCTRL
[
GCNT01-HMI
]
On
Function
“Automatic sequence control” is in progress
Double Command Blocking detected
*
2
Other devices traveling detected
*
3
DCB RCV OR
Traveling OR
ASEQ_MULTI_SEL
GCNT00IN_TMP_51
540001 800E00ED5A
SERI_ERR
&
&
1
≥
Unmatched condition detected *4
Serious error detection
From SOTFSW
*
1
S4301_STATE
Command blocking
*
1(S4301 defines
”Blocked”)
[
DPOS01-EN
]
On
Figure 3.7-7 Select condition logic for Reset in GCNT01
1
Note: “Command blocking” disables any operation except its own; the “command
blocking” is initiated by the status of “S4301” in a software switch controller
function (SOFTSW). The IEC 61850 standard defines “Command Blocking” as
“CmdBlk”. For more information on “S4301”, see Chapter
Control and monitoring
application: Software switch control function. (Table 3.7-3)
2
Note: “Double Command Blocking (DCB)” is an operation philosophy. It can be used to
protect the substation. The user can program it using GR-TIEMS. The DCB
operating signal is denoted as “DCB RCB OR” in Table 3.7-3.
3
Note: If the event “device-travelling” is detected, it indicates that another operator is
changing the status of a device. Thus, the IED should inhibit the operation of any
device for the duration that the event is detected. The detected signal is denoted
as “Traveling OR” in Table 3.7-3.
4
Note: Criteria “unmatched conditions” are decided when the “Test-bit status” in a
command is not identical to the “IED test status”.
5
Note: The user will need to program the PLC logic “Control hierarchy condition”. The
user is also required to connect the logic condition with the select condition logic
using the connection pint “GCNT00IN_TMP_51” (see Table 3.7-4). For more
information, see Chapter
Control and monitoring application: Control hierarchy.
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......