6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
91
ZS (Function ID
:
430001
)
Setting items
Range
Unit
Contents
Default
Note
1A rating
5A rating
1A
5A
Z3S-
MhoDX.EN
Off / On
-
Z3S directional-X characteristic use or not (for
Mho)
Off
Z3S-DX.Angle
0 - 60
deg Z3S directional-X characteristic angle
30
Quad
Z3S-X.Reach
0.10 -
500.00
0.01 -
100.00
- Z3S reactance reach
30.00
6.00
Z3S-R.Angle
30 - 90
deg Z3S resistive reach characteristic angle
75
Z3S-R.Reach
0.10 -
500.00
0.01 -
100.00
- Z3S resistive reach
25.50
5.10
Z3S-DX.Angle
0 - 60
deg Z3S directional-X characteristic angle
30
Z3S-DR.Angle
0 - 60
deg
Z3S directional-R characteristic angle (for
Quad)
5
TZ3S
0.00 - 100.00
s Z3S operation delay time
0.40
Output
Z3S-MSDET
Off / On
-
Multi-phase or non-earth-fault condition is
used or not
Off
Z3S-PSBBlk
Non / Block
- Z3S operation block or not by PSB detection
Non
Z3S-LEBlk
Non / Block
- Z3S blocked or not by Load encroachment
Non
Z3S-ARCBlk
Non / Block
- Autoreclose execution block by Z3S-trip
Block
Z3S-OCFS-EN
Off / On
- Fail-safe OC for Z3S-trip
Off
OCF3S
0.02 -
5.00
0.10 -
25.00
A Fail-safe OC operation level for Z3S-trip
0.20
1.00
Z3S-SOTF
Off / On
- SOTF using Z3S
Off
Z4S
Z4S-Dir
Forward / Reverse /
NonDir
- Z4S directional characteristic
Reverse
Mho
Z4S-Mho.Angle
30 - 90
deg Z4S mho characteristic angle (for Mho)
85
Z4S-Mho.Reach
0.10 -
500.00
0.01 -
100.00
- Z4S mho reach (for Mho)
20.00
4.00
Z4S-MhoX.EN
Off / On
- Z4S reactance reach use or not (for Mho)
Off
Z4S-X.Reach
0.10 -
500.00
0.01 -
100.00
- Z4S reactance reach
20.00
4.00
Z4S-MhoR.EN
Off / On
- Z4S resistive reach use or not (for Mho)
Off
Z4S-R.Angle
30 - 90
deg Z4S resistive reach characteristic angle
75
Z4S-R.Reach
0.10 -
500.00
0.01 -
100.00
- Z4S resistive reach
25.50
5.10
Z4S-
MhoDX.EN
Off / On
-
Z4S directional-X characteristic use or not (for
Mho)
Off
Z4S-DX.Angle
0 - 60
deg Z4S directional-X characteristic angle
30
Quad
Z4S-X.Reach
0.10 -
500.00
0.01 -
100.00
- Z4S reactance reach
20.00
4.00
Z4S-R.Angle
30 - 90
deg Z4S resistive reach characteristic angle
75
Z4S-R.Reach
0.10 -
500.00
0.01 -
100.00
- Z4S resistive reach
25.50
5.10
Z4S-DX.Angle
0 - 60
deg Z4S directional-X characteristic angle
30
Z4S-DR.Angle
0 - 60
deg
Z4S directional-R characteristic angle (for
Quad)
5
TZ4S
0.00 - 100.00
s Z4S operation delay time
0.60
Output
Z4S-MSDET
Off / On
-
Multi-phase or non-earth-fault condition is
used or not
Off
Z4S-PSBBlk
Non / Block
- Z4S operation block or not by PSB detection
Non
Z4S-LEBlk
Non / Block
- Z4S blocked or not by Load encroachment
Non
Z4S-ARCBlk
Non / Block
- Autoreclose execution block by Z4S-trip
Block
Z4S-OCFS-EN
Off / On
- Fail-safe OC for Z4S-trip
Off
OCF4S
0.02 -
5.00
0.10 -
25.00
A Fail-safe OC operation level for Z4S-trip
0.20
1.00
Z4S-SOTF
Off / On
- SOTF using Z4S
Off
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......