6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 683 -
4.6.3
Line-outage check
(i)
Voltage conditions
In the SYNCHK function the OVr, OVi, UVr, and UVi elements are used to verify the line-
condition. For example, when the user wishes to connect an incoming-line (i.e., transmission
line) with the running-line (i.e., a busbar), the voltage conditions on either lines may be
examined prior to connection. Alternatively, the absence of voltage on both lines may be
required before connection. In order to provide this functionality, the SYNCHK function has
four check zones to test for the line being either in-service or out-of-service; the four zones are
illustrated in Figure 4.6-7.
DRDI
LRDI
LRLI
DRLI
Setting [
UVI1
]
Setting [
OVI1
]
Setting [
UVR1
]
Vi
on the incoming line
Vr on the running line
Setting [
OVR1
]
Figure 4.6-7 Four voltage conditions examined in SYNCHK_Ry1
For example, “DRLI” zone covers the case when the running-line is out-of-service (DR)
and the incoming-line is in-service (LI). Table 4.6-4 exemplifies the areas in accordance with
the voltage conditions.
Table 4.6-4 Four voltage conditions and zones
Voltage condition
1
2
3
4
Area
D
○
R L
○
I
L
○
R L
○
I
D
○
R D
○
I
L
○
R D
○
I
○
R unning line (Vr)
(Dead)
(Live)
(Dead)
(Live)
○
I ncoming line (Vi)
(Live)
(Live)
(Dead)
(Dead)
Figure 4.6-8 and Figure 4.6-9 show the voltage-presence (or voltage-absence) check logic
used in the SYNCHK_Ry1 and Ry2 functions.
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......