(iv)
Mapping signals in signal list to Logical Nodes
The user can add or modify signal mapping to the LN variable. The following section describes
how to modify the mapped data if the user wants to add signals, which are sent using Report
or GOOSE.
Edit Mapping Data
1.
Search the signal to be sent from the Signal List window as shown in Figure
11.3-14.
2.
Drag and Drop the selected signal to the logical node variable.
Signals
Mapped data
Drag
Drop
Figure 11.3-14 Signal mapping
Note: To optimize the performance of the IED, “Period” should be 100 if the signal is not
required to be sent immediately.
The user should map a quality signal (i.e., Qual_Validity, U16_00, or U16_01)
should be mapped to “q” with Period=100.
The user should map a time signal (i.e., SYS_TIME) should be mapped to “t”.
Export / Import Mapping Data
The user can export mapped data in the CSV file; the user can edit the exported
CSV file by the MS-Excel® and import back into the GR-TIEMS. Figure 11.3-15
shows the export / import options.
Export Mapping Data
Import Mapping Data
Figure 11.3-15 Export / Import mapping data
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......