6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 1446 -
1.
Information list with regard to ‘Time tagged Measurand’
1.1 Events
Table 5-1.1
INF
Semantics
Contents
GI
Type
ID
COT
Function
Function
ID
Element ID
Name
16
Auto-reclose
active
OK status for the auto-
reclose operation
OK
1
1, 9
ARC
4A6001
8000011B60
ARC1 READY
11
Not applicable
12
ARC
4A6001
800001EBCF
ARC1 block signal
17
Tele-
protection
active
Not applicable
OK
1
1, 9
Carrier_D
istance
436001
8000001BB0
DISCAR_BLOCK;
inverted signal
12
No default setting
18
Protection
active
OK status for the
operation of the relays
OK
1
1, 9
DIF_LP
410001
8F00001BB2
DIFL_BLOCK;
inverted signal
12
No default setting
19 LED reset
'Trip LED reset' signal
is sent.
NA
1
1
LED
201B0
3100041001
LED-04; inverted
signal
11
Not applicable
12
Issued by GENERAL COMMAND
20
Monitor
direction
blocked
Forbidding to send the
IED message for the
upper level
OK
1
9,11
103SLV
304001
3100003602
103BLK
21 Test mode
Available of test mode
OK
1
9,11
103SLV
304001
3100003601
103TST
22
Local
parameter
setting
OK
1
Not applicable
23 Characterist1
Available for group
setting #1
OK
1
1, 9
103SLV
304001
8020011001
AG1STAT
11
Not applicable
12
Issued by GENERAL COMMAND
24
Characteristic
2
Available for group
setting #2
OK
1
1, 9
103SLV
304001
8120021001
AG2STAT
11
Not applicable
12
Issued by GENERAL COMMAND
25
Characteristic
3
Available for group
setting #3
OK
1
1, 9
103SLV
304001
8220031001
AG3STAT
11
Not applicable
12
Issued by GENERAL COMMAND
26
Characteristic
4
Available for group
setting #4
OK
1
1, 9
103SLV
304001
8320041001
AG4STAT
11
Not applicable
12
103SLV
304001
8320046422
AG4CMD
27
Auxiliary
input1
Reception
of
the
signal#1 generated at
an auxiliary contact
OK
1
1, 9
Issued by GENERAL COMMAND
28
Auxiliary
input2
Reception
of
the
signal#2 generated at
an auxiliary contact
OK
1
1, 9
Issued by GENERAL COMMAND
29
Auxiliary
input3
Reception
of
the
signal#3 generated at
an auxiliary contact
OK
1
1, 9
Issued by GENERAL COMMAND
30
Auxiliary
input4
Reception
of
the
signal#4 generated at
an auxiliary contact
OK
1
1, 9
Issued by GENERAL COMMAND
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......