6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 307 -
VT failure detection (VTF)
If a failure occurs on the secondary circuit in the voltage transformer (VT), the operation in
relays cannot be obtained properly because the relays do not measure voltages correctly.
Therefore, the VT failure detection (VTF) function is provided to block operating the relays
upon occurrence of the VT failure. Accordingly, if a VT failure is detected by the VTF function,
an alarm signal is issued for the relays upon occurrence of the VT failure. Accordingly, an
alarm signal is issued if a VT failure is detected by the VTF function; a detection signal by the
VTF function blocks operating the relay for the voltage monitor
1
.
After the disappearance of the VT failure, the VTF function can take account of the VT
secondary circuit being in healthy condition in the three-phase; the operation of the VTF
function is reset
2
. Thus, the blocked relays are allowed to operate again. Incidentally, issuing
the VTF alarm is automatically removed and then the user can find resetting the VTF alarm.
1
Note: The VTF function can block the operation in several relays, but it does not block
the operation in other relays. To know the blocking, refer sections of the respective
protection functions.
2
Note: The user can programmable the operation using the setting and the PLC signals.
(2.62.0)
─────────────────────────────────────────────────────────────────
Note:
The implementation of particular features is dependent upon the selection of
hardware and the configuration of functions. Several IED models do not support certain
features. To determine whether a particular feature has been implemented within an IED,
identify the IED ordering number; and check the order number for the “G&T position” whilst
referring to the comparison table below. For more information, see
Appendix: Ordering
.
Table 2.21-1 Comparative table in respective ordering numbers
Sec.
Feature
Ordering No. at “G&T”
31
32
–
Main features
✓
✓
✓
: Applicable NA: Not applicable
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......