6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 806 -
Signal Number
Signal Name
Description
M/O
513001 820403ED50
TPOS03IN_TMP_21
TPOS03 control hierarchy condition(PLC#3)
M
…
…
….
513001 820418ED50
TPOS24IN_TMP_21
TPOS24 control hierarchy condition(PLC#3)
M
Table 4.9-9 PLC monitoring points (Output signal for select condition logic)
Signal Number
Signal Name
Description
513001 8004011F54
TPOS01_SC_ST_ERR
TPOS01 select command mode is invalid.
513001 8004021F54
TPOS02_SC_ST_ERR
TPOS02 select command mode is invalid.
513001 8004031F54
TPOS03_SC_ST_ERR
TPOS03 select command mode is invalid.
…
…
…
513001 8004181F54
TPOS24_SC_ST_ERR
TPOS24 select command mode is invalid.
513001 8204011F59
TPOS01_QLT_SPP
Event suppression detected (TPOS01)
513001 8204021F59
TPOS02_QLT_SPP
Event suppression detected (TPOS02)
513001 8204031F59
TPOS03_QLT_SPP
Event suppression detected (TPOS03)
…
…
…
513001 8204181F59
TPOS24_QLT_SPP
Event suppression detected (TPOS24)
513001 8604011F5A
TPOS01_QLT_BI_ERR
BI connection error detected(TPOS01)
513001 8604021F5A
TPOS02_QLT_BI_ERR
BI connection error detected(TPOS02)
513001 8604031F5A
TPOS03_QLT_BI_ERR
BI connection error detected(TPOS03)
…
…
….
513001 8604181F5A
TPOS24_QLT_BI_ERR
BI connection error detected(TPOS24)
Table 4.9-10 PLC monitoring points (Output signal for BIO)
Signal Number
Signal Name
Description
513001 8A04011DC4
TPOS01_P1SL_BO_FLG Select command (P1) for Binary Output in TPOS01
513001 8A04021DC4
TPOS02_P1SL_BO_FLG Select command (P1) for Binary Output in TPOS02
513001 8A04021DC4
TPOS03_P1SL_BO_FLG Select command (P1) for Binary Output in TPOS03
…
…
…
513001 8A04181DC4
TPOS241SL_BO_FLG
Select command (P1) for Binary Output in TPOS24
513001 8A04011DC6
TPOS01_P2SL_BO_FLG Select command (P2) for Binary Output in TPOS01
513001 8A04021DC6
TPOS02_P2SL_BO_FLG Select command (P2) for Binary Output in TPOS02
513001 8A04031DC6
TPOS03_P2SL_BO_FLG Select command (P2) for Binary Output in TPOS03
…
….
….
513001 8A04181DC6
TPOS24_P2SL_BO_FLG Select command (P2) for Binary Output in TPOS24
513001 8A04011DC8
TPOS01_P3SL_BO_FLG Select command (P3) for Binary Output in TPOS01
513001 8A04021DC8
TPOS02_P3SL_BO_FLG Select command (P3) for Binary Output in TPOS02
513001 8A04031DC8
TPOS03_P3SL_BO_FLG Select command (P3) for Binary Output in TPOS03
…
….
….
513001 8A04181DC8
TPOS24_P3SL_BO_FLG Select command (P3) for Binary Output in TPOS24
(xii)
Setting names
Table 4.9-11 Settings for ‘SBO control in TPOSxx
Setting Name
Description
Default
Setting item or value
TPOSxx-CTREN
Activation of the control function in TPOS01
–
24
On
Off / On
TPOSxx-LGSLFFCT
Logic selector for select condition (TPOS01
–
24)
Fixedlogic
Fixedlogic / PLC
TPOSxx-DEVTYPE
Equipment(EDS or 43SW) type selector
switch
switch / EDS
TPOSxx-CTRHMI
Activation for the panel control locally (TPOS01
–
24)
On
Off / On
Note: The “xx” within “TPOSxx” represents the function number. If TPOS03 is
considered, “xx” is equal to “03”. The suffix “xx” can be represented from 01 to 24.)
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......