6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 294 -
2.18.5
Setting
OSTZ(Function ID: 478001)
Setting items
Range
Unit
Contents
Default
Note
1A rating
5A rating
1A
5A
OSTZ-EN
Off / On
- OSTZ protection scheme switch
Off
OSTZ-R1
15.00 -
150.00
3.000 -
30.000
- OSTZ resistive reach (at Right side)
25.50
5.100
OSTZ-R2
5.00 -
50.00
1.000 -
10.000
- OSTZ resistive reach (at Left side)
12.50
2.500
OSTZ-XF
5.00 -
250.00
1.000 -
50.000
- OSTZ reactive reach (at Forward side)
30.00
6.000
OSTZ-XB
1.00 -
50.00
0.200 -
10.000
- OSTZ reactive reach (at Backward side)
5.00
1.000
TOSTZ1
0.01 - 1.00
s OSTZ out-of-step timer
0.04
TOSTZ2
0.01 - 1.00
s OSTZ out-of-step timer
0.04
OSTZ-Output
Trip / BO
- OSTZ trip signal output position
Trip