6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 1226 -
(ii)
Setting of time-tagged messages
In Time-tagged message frame in the IEC 60870-5-103 standard, event information and
status information are responded for Class 1 request from the upper system (station). The
GR-series relay can provide event information and status information by Time-tagged
message frame about the signal assigned to a Data ID of the signal list.
When the “Time-tagged message” tab is selected, the “Time-tagged message” setting
screen is displayed on the start screen.
Figure 11.4-5 Time-tagged message in the GR-TIEMS
Type ID=1 (Time-tagged message) or Type ID=2 (Time-tagged message with relative
time) can be set in this screen. In one frame of Time-tagged message, the Type ID, INF,
FUN, DPI and COT must be set and the maximum 256 frames of Time-tagged message can
be set. The information number of the frame is determined by the INF setting. The most
left item “No.” is only serial number and can be skipped.
Common address is linked with the address setting† in the IEC 60870-5-103 standard.
†Note: For more information, see
Appendix: IEC 60870-5-103 interoperability.
In the transmission format of Type ID=1 (Time-tagged message) and Type ID=2 (Time-
tagged message with relative time), customized items are shown in Table 11.4-3 and Table
11.4-4.
Table 11.4-3 Time-tagged message (Type ID=1)
Oct.
Item
Value
Remarks
1
Start
68H
2
Length
14
3
Length
14
4
Start
68H
5
Control field
08H+ACD+D
FC
6
Address
1-254
Setting from the relay
7
Type identification (Type ID)
1
Customized by GR-TIEMS
8
Variable structure qualifier
81H
9
Cause of transmission (COT)
1/9/11/12
Customized by GR-TIEMS
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......