and monitoring application: Automatic sequence control function.
*Note: The LEDR function can run on either “the SBO mode” or “the DIR mode” using a
“ctlmodel” signal when the communication is carried out in the IEC61850; thus,
mapping is required for the IEC61850 communication.
(ii)
Output signal required mapping
The LEDR function can issue a “Select success” signal at the output point
“LEDR01_NSD_CSF”, when the LEDR function determines that the input signal “Select
command (reset)” is true. If the LEDR function determines that the “LEDR01_NSD_CSF” is
not true, the LEDR function returns to the “Wait for a next command” stage.
(iii)
Select condition
Figure 3.6-3 shows the select condition logic in the LEDR function.
Select condition
LEDR function (Function ID: 528001)
To selection logic
Control hierarchy (e.g. 43RL) (PLC connection point) *5
IED serious error detected
[
LEDDR1_EN
]
On
Users must setup this condition correctly
Function
“Automatic sequence control” is in progress
S4301_STATE
Command blocking
*
1 (S4301 defines
”Blocked”)
Double Command Blocking detected
*
2
Other devices traveling detected
*
3
DCB RCV OR
Traveling OR
ASEQ_MULTI_SEL
LEDR01_CTRL_RIGHT
528001 820701ED50
SERI_ERR
&
&
1
≥
Unmatched condition detected *4
Figure 3.6-3 Select condition logic in LEDR
*6
*1
Note:
“command blocking” disables any operation except its own: the “command
blocking” is initiated by the status of “S4301” in a software controller (SOFTSW).
The IEC 61850 standard defines “command blocking” as “CmdBlk”. For more
information on S4301, see Chapter
Control and monitoring application: Software
switch control function. See the signal “S4301_STATE” of Table 3.6-2.
*2
Note:
“Double Command Blocking (DCB)” is an operation philosophy in the
common control function (CMNCTRL). It can be used to protect the substation.
The user can program it using GR-TIEMS. The DCB operating signal is denoted
as “DCB RCV_OR in Table 3.6-2. For more information, see Chapter
Control and
monitoring application: Common controls.
*3
Note:
If the event “device-travelling” is detected in the CMNCTRL function, it
indicates that another operator is changing the status of a device. Thus, the IED
should inhibit the operation of any device for the duration that the event is
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......