6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 520 -
(ii)
Receiving “operate command Off” from the remote end
Figure 4.1-21 depicts the reception of the operate command for ‘Off’ from the remote-end.
Signal reception in
IEC61850
Off control from remote-end
Do nothing
Operation
decision
Success
Failed
Operate logic
Wait for a command
Signal output
On control from front-panel
Off control from front-panel
On control from remote-end
On control by PLC function
Off control by PLC function
Wait for a next command
Select logics
Select command Off from remote-end
Select command On from remote-end
Select command Off from front panel
Select command On from front panel
Select command On by the PLC
function
Select command Off by the PLC
function
Figure 4.1-21 Outline of operate command ‘Off’
Mapping required for Input point from communication
Figure 4.1-22 illustrates the operate logic when an “Operate command Off (Remote-Off-
Control)” signal is applied to the SPOS01 logic. The input-point “DEV01_CONTROL_REQ” is
used for the reception of the “Operate command Off (Remote-Off-Control)”.
SPOS01 function (Function ID: 510001)
Assign to BOs
Operate Cmd.
with ILK
† condition
[
SPOS01-PLSM
]
*
Var
Fix
S
R
Operation Failed
0
t
1.0s- 100.0s
0.1
– 50.0 s
[
SPOS01-RST
]
[
SPOS01-CPW
]
Operation Cmd.
without ILK
† condition
Operate condition
‡
[
SPOS01-LGCTRCON
]
Fixedlogic
Fixedlogic
[
SPOS01-LGCFEXOT
]
DEV01_CONTROL_REQ
Command
“Remote-Off-Control”
510001
_
7001016D08
ILK
†
condition (“Off”) passed
SPOS01-Off
ASEQ
§ function
is in progress
ASEQ_MULTI_SEL
SPOS01IN_TMP_34
510001 800101EE56
User Configurable condition
(PLC#3 connection point)
SPOS01IN_TMP_42
510001 810101EDDA
User Configurable condition
(PLC#2 connection point)
“SPOS01-EX_CMP
(5A0101
_
8001011E93)
“SPOS01-FEC_OK_CSF”
(510001
_
8001011E7F)
&
&
1
≥
&
1
≥
1
≥
&
&
&
&
“SPOS01_FEX_BO”
§§
(510001
_
8101011DD0)
“SPOS01_EX_FFL”
†
†
(510001
_
8601011E91)
To PLC
logic
Input
Output
Operate logic in SPOS01
To BO connection
To
“Wait for a command”
Figure 4.1-22 Operate ‘Off’ from the remote -end in SPOS01
††
†Note: The ILK function can provide the operation criteria for “Off”.
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......