6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 271 -
Pick-up characteristic
The IDMT characteristic is applied when the operation of the UVS1 element is required
inversely in accordance with the level of input voltage. The IDMT characteristic curve is
illustrated in Figure 2.16-2 using a value of time multiplier is set for [
UV1-TMS
]. It is followed
to Equation (2.16-1) in conformed in IEC 60255-127
t(G) = TMS × {[
𝑘
1 − (𝑉 𝑉
𝑠
⁄ )
𝑎
] + 𝑐}
(2.16-1)
where,
t = operating time (seconds),
V = energizing voltage (voltage),
Vs = pickup voltage setting (voltage),
TMS = time multiplier setting.
Except for pre-programmed characteristics, the user can have a user-programmable
(original) characteristic curve. The user-programmable (original) curve is obtained when the
constants of k, a, c, as shown in Table 2.16-2, are set, and when
Original
is set for scheme
switch [
UVS1-Timer
]. The constants are set with settings [
UVS1-k
], [
UVS1-a
], and [
UVS1-C
].
Figure 2.16-2 IDMT characteristics curves depending on TMS
1.000
10.000
100.000
1000.000
0
0.2
0.4
0.6
0.8
1
Op
erat
in
g
T
im
e
(secs
)
Applied Voltage (x Vs)
Undervoltage Inverse Time Curves
TMS=5
TMS=10
TMS=2
TMS=1
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......