6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 599 -
Settings for extra contact health check (special setting, example #3)
Figure 4.2-51 shows an additional setting example for the 43SW scheme; one of the settings is
made hypothetically. That is, the point “DPSY01_OSL_BO_FLG” is actually chosen for the
setting [
DPSY01-OSLBORD
]; i.e. BO1-RB is not chosen for this selection. This special example
can issue a select command, which is called “operated by internal select function”. The user
does not need to consider the use of a BO circuit for a select command, when there are no BO
circuits available.
Table 4.2-33 Extra setting example for contact health check
Example #3
Setting for example #3
“DPSY01_OSL_BO_FLG” is not connected to any BO
[DPSY01-OSLBORD] =” DPSY01_OSL_BO_FLG”
OK
“DPSY01_FSL_BO_FLG” is not connected to any BO
[DPSY01-FSLBORD]=” ” DPSY01_OSL_BO_FLG”
OK
“DPSY01_OEX_BO_CSF” is connected to “BO3” at IO#1
[DPSY01-OEXBORD]=” 200B018202021113” (BO3-RB)
OK
“DPSY01_FEX_BO_CSF” is connected to “BO4” at IO#1
[DPSY01-OEXBORD]=” 200B018202031113” (BO4-RB)
OK
Plus (+)
Drivers
BO3
“BO4-RB”
(200B01
_
8302031113)
BO4
“BO3-RB”
(200B01
_
8202021113)
SW4 is driven with
BO4 at IO#1
Local/Remote-end
SW 3
SW 1
Minus (
−)
BIO module
43SW
SW 2
SW 4
SW3 is driven with
BO3 at IO#1
SW1 is not driven with
any BO
SW2 is not driven with
any BO
Physical BOs
are virtualized.
“DPSY01_OSL_BO_FLG”
(511001 8602011DC6)
Select command
Closing
Operate command
Closing
“DPSY01_OEX_BO”
(511001 8202011DD3)
Operate command
Open
“DPSY01_FEX_BO”
(511001 8102011DD0)
Closing
command
Select command
Open
“DPSY01_FSL_BO_FLG”
(511001 8A02011DC4)
Open
command
Figure 4.2-51 Contact health check setting and 43SW diagram for example #3
Table 4.2-34 PLC monitoring points (Output signal for event suppression function in DPSY)
Signal Number
Signal Name
Description
511001 3102011001
DPSY01_3PH_STATE
DPSY01 3ph_state
511001 3102021001
DPSY02_3PH_STATE
DPSY02 3ph_state
511001 8102011F5F
DPSY01_F_QLT_SPP
Event suppression detected (DPSY01)
511001 8102021F5F
DPSY02_F_QLT_SPP
Event suppression detected (DPSY02)
Table 4.2-35 PLC monitoring points (Output of select signal in DPSY)
Signal Number
Signal Name
Description
511001 8602011DC6
DPSY01_OSL_BO_FLG DPSY01 select (CLOSE) command for Binary Output.
511001 8602021DC6
DPSY02_OSL_BO_FLG DPSY02 select (CLOSE) command for Binary Output.
511001 8A02011DC4
DPSY01_FSL_BO_FLG
DPSY01 select (OPEN) command for Binary Output.
511001 8A02021DC4
DPSY02_FSL_BO_FLG
DPSY02 select (OPEN) command for Binary Output.
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......