6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 1317 -
Changing rated current
A rated current (In) has been set by the manufacture†, but the user can change it to the other
(either 1A or 5A) by yourself. Follow the steps below, as shown in the table:
Table 13.4-1 Change rated current workflow
Index
Workflow
Note
Check
it out
yourself
Step1 Power-off the IED
BO circuits are locked after power-off.
Step2 Change CPU mode
An optional jumper required
Step3 Change rated currents
Optional jumpers required
Step4 Take back to the original
Restoring the modules
Step5 Check altered ordering code
Confirm it has been changed
Step6 Write settings with altered code Choose the altered ordering code
Step7 DEP setting confirmation
Check DEP settings for Ch*
Step8 Memo for change rated current
(Keep it for your future reference)
†Note: To confirm, see Factory setting label on the case side. For more detail, see
Preceding Section
Unpack and inspection of hardware and software.
Step1: Turn off the IED.
Note that all outputs are locked-out when powered-off†.
Then, open the IED panel. Remove a flat cable and lateral beams in the IED case‡.
†Note: For alarm outputs, refer
to
Chapter Automatic supervision: Error outputs
with contacts and binary output circuits.
Remind that alarms are dependent
on the alarm degree. See
Table ‘FAIL contact, BO, LED outputs depending
on levels’
‡Note: For removal and restoration of inner modules, see
Guide for replacement of
inner modules, separately:
—For type using compression terminals
(6F2S1955)
—For type using ring terminals
(6F2S1956)
Step2: Change CPU mode (Default
Constrained mode)
To change a CPU mode†, the user shall close a CPU-W6 circuit with a jumper. The
user can get jumpers from an optional-kit (EP-221). Insert the jumper on either W6(1-
2) or W6(3-4) for changing.
†Note: To find
the CPU location, go to Chapter
Technical description: Signal
processing and communication module,
and see
Figure Configuration switch
about the mode.
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......