6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 730 -
DPOS01 function (Function ID:
512001)
“DPOS01_FSL_BO_CSF”
(512001
_
8A03011DC4)
DEV01_OP_INTERLOCK
Operate command
without ILK
† condition
ILK
† condition (“OFF”) passed
PLC in DIR operate
For DIR operation
512001 800301EE31
Signals from user PLC logic
Output
Select logic in DPOS01
0.1s
0
t
0.6s
0
t
&
&
&
Select condition
‡
1
≥
OFF-control command requiring
ILK† checking
(PLC#1 connection point)
DEV01_OP_COMMAND
512001 800301EE30
OFF-control command requiring no
ILK† checking
(PLC#2 connection point)
Operate command with
ILK
† condition
DPOS01-Open
Select
“Failed”
To BO connection
Select
“success”
To
“Wait for a command”
For DIR operation
Figure 4.8-12 Select ‘Off’ by the PLC function in DPOS01
††
†Note: The ILK function provides the operation criteria for “Off”.
‡Note: A “select condition” signal is provided from the select condition scheme. For more
information, see Figure 4.8-13.
††
Note: To identify the input and output points of the other DPOS logics, see Table 4.8-3
for the inputs (PLC#1 and PLC#2) and Table 4.8-9 for the outputs.
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......