6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 846 -
PLC
BO4_SOURCE
200B01 310203E11D
“TPOS01_P1EX_BO”
(513001
_
8104011DD0)
Operate logic in TPOS01
PLC connection point in BO4
Operate logic for
P1-control
in TPOS01
≥1
&
[
BO4_CPL
]
Off
On
&
DRIVER BO4
Signal designated by
setting [
Input signal 1
]
[
Input signal 2
]
[
Input signal 3
]
[
Input signal 4
]
[
Input signal 5
]
[
Input signal 6
]
[
Input signal 7
]
[
Input signal 8
]
Operate
command
P1
≥1
“BO4”
(200B01
_
8302031112)
“BO4-RB”
(200B01
_
8302031113)
BO4
–BO6 circuit at IO#1 (Function ID: 200B01)
Terminal and
wire
To contact health
check
BO5_SOURCE
200B01 310204E11D
“TPOS01_P2EX_BO”
(513001
_
8204011DD3)
PLC connection point in BO5
Operate logic for
P2-control
in TPOS01
≥1
&
[
BO5_CPL
]
Off
On
&
DRIVER BO5
Signal designated by
setting [
Input signal 1
]
[
Input signal 2
]
[
Input signal 3
]
[
Input signal 4
]
[
Input signal 5
]
[
Input signal 6
]
[
Input signal 7
]
[
Input signal 8
]
Operate
command
P2
≥1
“BO5”
(200B01
_
8402041112)
“BO5-RB”
(200B01
_
8402041113)
To contact health
check
To contact health
check
To contact health
check
Connected by
“Programming”
Connected by
“Programming”
BO6_SOURCE
200B01 310205E11D
“TPOS01_P3EX_BO”
(513001
_
8204011DD6)
PLC connection point in BO6
Operate logic for
P3-control
in TPOS01
≥1
&
[
BO6_CPL
]
Off
On
&
DRIVER BO6
Signal designated by
setting [
Input signal 1
]
[
Input signal 2
]
[
Input signal 3
]
[
Input signal 4
]
[
Input signal 5
]
[
Input signal 6
]
[
Input signal 7
]
[
Input signal 8
]
Operate
command
P3
≥1
“BO6”
(200B01
_
8502051112)
“BO6-RB”
(200B01
_
8502051113)
To contact health
check
To contact health
check
Connected by
“Programming”
Figure 4.9-58 Example of operate commands connected with BO4-BO2
†Note: Table 4.9-20 shows the remaining signals except for “TPOS01”.
(iv)
Contact health check
The TPOS01 function has contact health check feature for the BO circuits; hence, the user is
able to connect an output signal to the contact health check function when
Fixedlogic
is set for
scheme switches [
TPOS01- LGP1EXOT
] to [
TPOS01-LGP3EXOT
]†. Consequently, the TPOS01
function can determine whether the signal has been successfully output from the BO. If a
failure is reported, the TPOS01 function determines that the signal is not output successfully
to the BO; then the command is canceled immediately and the TPOS01 function returns to the
“Wait for a command” stage.
†Note: Table 4.9-21 shows settings for the health check feature in the other TPOS
functions.
Setting for “select command P1/P2/P3”
For example, the point”TPOS01_P1SL_BO” is connected to the BO1 circuit for the issuing of
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......